Inspection and testing

What the standards require

  • Visual inspection and testing of construction wiring switchboards every six months.
  • Portable safety switches need daily checking using pushbutton test before use and then every three months by a competent person.
  • Fixed safety switches require monthly pushbutton test and then every 12 months by a competent person.
  • Relocatable construction premises tested every six months. This includes site sheds and amenities.
  • Electrical equipment on construction and demolition sites, every three months.
  • All records of inspection and tests are to be kept.
  • Records are to include:
    • register of all equipment
    • record of formal inspections and tests
    • repair register
    • record of faulty equipment.
  • Tag new equipment with test or re-test date.
  • Fit a durable, non-reusable, non-metallic tag to compliant equipment.
  • Construction wiring, switchboards, fixed safety switches, fixed and transportable equipment do not need to be tagged.
  • Non-compliant equipment must be taken out of use immediately. A warning label should be attached before sending it for repair or disposal.

Contacts

Electrical safety infoline

1300 650 662 (local call charge within Australia, mobiles charged at applicable rates)

SmartLicence

Contact SmartLicence on 1300 363 711 for applications for licences, permits and registration information and assistance

Trades Recognition Australia

Visit Trades Recognition Australia (non-Queensland Government link) for more information on national recognition of your electrical trade skills.
Last reviewed
1 February 2010
Last updated
9 March 2012

Rate this page

  1. How useful was the information on this page?
 
Close window

Send this page to a friend

*
*
*